Ames-fire-waterworks 933GS Stainless Steel Electronic Control Valve (fo Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Ausrüstung Ames-fire-waterworks 933GS Stainless Steel Electronic Control Valve (fo herunter. Ames Fire & Waterworks 933GS Stainless Steel Electronic Control Valve (for Electric Valve Positioning) User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 1
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
01/06
930 Series
Model
8550 Hansen Road Houston, Texas 77075 (Ph) 713.943.0688 (Fx) 713.944.9445 www.amesrewater.com
ELECTRONIC CONTROL VALVE
(for Electric Valve Positioning)
933
633
933 link
Operation
The AMES Model 933 / 633 Electronic Control Valve is designed to be electrically positioned to control ow,
pressure, level or temperature for water applications. It is a throttling valve controlled by two 2-way solenoids
installed in the pilot control system, one connecting the valve cover chamber with upstream pressure and
the other connecting the main valve cover chamber downstream. By alternately energizing the solenoids,
line pressure is admitted to or relieved from the cover chamber of the main valve, allowing the valve to be
“positioned” to maintain a desired value.
The valve is normally interfaced with SCADA systems or a Programmable Logic Controller that compares a
Process Variable (PV) to a desired setpoint, and energizes the solenoid pilots to throttle the valve open or
closed until the PV reaches the desired setpoint.
Rate of valve operation is controlled by separate adjustable Opening and Closing Speed Controls that
control the rate uid and pressure are admitted to or relieved from the main valve cover chamber.
The valve is constructed with two “normally closed” solenoids allowing the valve to “hold last position”
upon power failure. The valve may also be congured to open fully or close drip tight upon power failure if
desired.
Specify valve to “hold last position”, “open fully” or “close drip tight” upon power failure prior to
ordering.
Installation Guidelines
• Prior to installation, ush line to remove debris.
• Install valve horizontally “in line” (cover facing UP), so ow arrow matches ow through the line. Avoid
installing valves 6” and larger vertically. Consult factory prior to ordering if installation is other than
described.
• Install inlet and outlet isolation valves. NOTE: When using buttery valves, insure disc does not contact
control valve. Damage or improper valve seating may occur.
• Provide adequate clearance for valve servicing and maintenance.
• Install pressure gauges to monitor valve inlet and outlet pressure.
• Connect Solenoid Pilots to appropriate power source in compliance with local electrical codes.
Other AMES Solenoid Control Valves
930 / 630 Solenoid (On-Off) Valve (4” & smaller)
930-01 / 630-01 Solenoid (On-Off) Valve with Hydraulic Check Feature (4” & smaller)
930-19 / 630-19 Solenoid (On-Off) Valve (6” & larger)
930-01-19 / 630-01-19 Solenoid (On-Off) Valve with Hydraulic Check Feature (6” & larger)
Seitenansicht 0
1

Inhaltsverzeichnis

Seite 1 - 930 Series

01/06930 SeriesModel8550 Hansen Road • Houston, Texas 77075 • (Ph) 713.943.0688 • (Fx) 713.944.9445 • www.amesrewater.comELECTRONIC CONTROL V

Kommentare zu diesen Handbüchern

Keine Kommentare