Ames-fire-waterworks 952GS Stainless Steel Rate-of-Flow Control Valve w Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Ausrüstung Ames-fire-waterworks 952GS Stainless Steel Rate-of-Flow Control Valve w herunter. Ames Fire & Waterworks 952GS Stainless Steel Rate-of-Flow Control Valve with Pressure Sustaining Feature User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 1
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
01/06
950 Series
Model
8550 Hansen Road Houston, Texas 77075 (Ph) 713.943.0688 (Fx) 713.944.9445 www.amesrewater.com
RATE-OF-FLOW VALVE with
PRESSURE SUSTAINING FEATURE
952
652
Operation
The AMES Model 952 / 652 Rate of Flow Control Valve with Pressure Sustaining Feature is designed to
automatically limit ow rate to a constant, adjustable, maximum, and sustain a minimum upstream pressure.
The ow control action of the valve is controlled by a normally open, differential control pilot designed to: 1)
Open (allowing uid out of the main valve cover chamber) when the differential pressure across the orice
plate is below it’s adjustable set point, and, 2) Close (allowing uid to ll the main valve cover chamber) when
the differential pressure across the orice plate is above it’s adjustable set point. A decrease in differential
pressure causes the valve to modulate towards an open position, increasing ow rate. An increase in
differential pressure causes the valve to modulate towards a closed position, decreasing ow rate.
The normally closed sustaining pilot remains open when upstream pressure is above the adjustable setpoint,
and modulates toward a closed position if upstream pressure falls below the setpoint. As the sustaining pilot
closes, uid is directed into the main valve cover chamber, allowing the valve to modulate toward a closed
position, raising upstream pressure. Normal ow control operation resumes when upstream pressure is
above the sustaining pilot setpoint.
The Orice Plate Assembly should be installed three to ve pipe diameters downstream of the Model
952 / 652, and eld connected with 3/8” minimum copper tubing in accordance with factory piping
schematic. Please specify desired ow rate prior to ordering.
Installation Guidelines
• Prior to installation, ush line to remove debris.
• Install valve horizontally “in line” (cover facing UP), so ow arrow matches ow through the line. Avoid
installing valves 6” or large vertically. Consult factory prior to ordering if installation is other than
described.
• Install inlet and outlet isolation valves. NOTE: When using buttery valves, insure disc does not contact
control valve. Damage or improper valve seating may occur.
• Provide adequate clearance for valve servicing and maintenance.
• Install pressure gauges to monitor valve inlet and outlet pressure.
• Install Orice Plate Assembly (provided) 3 to 5 pipe diameters downstream of the 950 / 650 with the
sensing connections offset from top of pipeline to avoid air accumulation. The Orice Plate Assembly
should not be installed next to a buttery valve.
• Connect Orice Plate Assembly to Rate-of-Flow Pilot using 3/8” diameter minimum copper tubing (eld
installed) in accordance with factory piping schematic.
Other AMES Rate-of-Flow Control Valves
950 / 650 Rate-of-Flow Control Valve
950-01 / 650-01 Rate-of-Flow Control Valve with Hydraulic Check Feature
950-15 / 650-15 Rate-of-Flow Control Valve with Solenoid (On-Off) Feature
951 / 651 Rate-of-Flow Control Valve with Pressure Reducing Feature
Seitenansicht 0
1

Inhaltsverzeichnis

Seite 1 - 950 Series

01/06950 SeriesModel8550 Hansen Road • Houston, Texas 77075 • (Ph) 713.943.0688 • (Fx) 713.944.9445 • www.amesrewater.comRATE-OF-FLOW VALVE w

Kommentare zu diesen Handbüchern

Keine Kommentare